Introduction
The LP33 Series is a robust, high performance UPS system
suitable for broad range of mission critical applications
including small data centers, medical, manufacturing,
industrial, telecom and commercial buildings.
Design and Performance
The
LP33 Series uses double conversion topology with a
true on-line
VFI (voltage frequency independent) design.
The hybrid
IGBTrectifier provides low input THD(total harmonic
distortion) and high input power factor. The
IGBT inverter
section with transformerless output ensures low output
distortion and fast transient response.
High Efficiency
The
LP33 Series can operate in high efficiency Eco Mode with
efficiencies up to 98% across a broad range of the operating
load range. Eco Mode operation continuously monitors
the output voltage and frequency, and will instantaneously
switch to inverter during voltage or frequency disturbance
to ensure compliance with the
ITI (CBEMA) curve.
Redundant Parallel Architecture
™
(RPA
™
)
Redundant Parallel Architecture
™
(RPA
™
) can be used
to parallel up to four (4)
LP33 units for redundancy or
capacity. The
RPA
™
system eliminates single points of
failure by using redundant controls and integral static
switches eliminating centralized bypass cabinets; and
allows field addition of future modules for load growth.
Service
The
LP33 Series is fully supported by GE’s Global Services
team, providing world-class, 7x24 emergency service
along with preventive maintenance, training, spare
parts depots and application expertise.
Features and Benefits
>
208
V Transformerless design for smaller footprint,
less weight and improved efficiency
>
High Efficiency Eco Mode up to 98% efficiency for
single module configuration
>
High input power factor (>.98) and low input distortion
(<10%) provided by a hybrid
IGBT rectifier, prevents
disturbances to other electrical equipment, eliminating
the need for filters or oversized feeders
>
Compact footprint, front service access, easily trans-
portable, robustly designed system with low audible noise,
suitable for both office and industrial environments
>
Utilizes high-frequency
PWM (Pulse Width Modulation)
IGBT digital control technique, resulting in extremely
low output distortion and fast transient response
>
Redundant Parallel Architecture
™
(RPA
™
) increases
system reliability by eliminating single points of failure
>
Intelligent Energy Management (
IEM) while
operating multiple units in
RPA
™
, the IEM optimizes
double conversion efficiency
>
Very wide
AC-input voltage and frequency
capability minimizes the need to switch to batteries,
resulting in increased battery life
>
Superior Battery Management (
SBM) enhances
battery life and reduces cost of operation
>
Integrated internal manual maintenance bypass
reduces the need for external equipment
GE Digital Energy
Power Quality
LP33 Series
Uninterruptible
Power Supply (
UPS)
10-100kVA, UL Listed